Kilowatts to volts calculator
to calculator.
Enter the in kilowatts, in amps and press the Calculate button to get the in volts:
DC kilowatts to volts calculation
The voltage V in volts (V) is equal to 1000 times the power P in kilowatts (kW), divided by the current I in amps (A):
V(V) = 1000 × P(kW) / I(A)
AC single phase kilowatts to volts calculation
The voltage V in volts (V) is equal to 1000 times the power P in kilowatts (kW), divided by the PF times the current I in amps (A):
V(V) = 1000 × P(kW) / (PF × I(A) )
AC three phase kilowatts to volts calculation
The line to line RMS voltage VL-L in volts (V) is equal to 1000 times the power P in kilowatts (kW), divided by square root of 3 times the PF times the current I in amps (A):
VL-L(V) = 1000 × P(kW) / (√3 × PF × I(A) )
≈ 1000 × P(kW) / (1.732 × PF × I(A) )
Additional explanations and examples
How to convert kilowatts to volts
How to convert in to in .
You can calculate volts from kilowatts and , but you can't convert kilowatts to volts since kilowatts and volts units do not measure the same quantity.
DC kW to volts calculation formula
The voltage V in volts is equal to 1000 times the power P in kilowatts, divided by the current I in amps:
V(V) = 1000 × P(kW) / I(A)
So volts are equal to 1000 times kilowatts divided by amps.
volt = 1000 × kilowatts / amp
or
V = 1000 × kW / A
Example
What is the voltage in volts when the power consumption is 4 kilowatts and the current flow is 3 amps?
V = 4 kW / 3A = 1333.333V
AC single phase watts to volts calculation formula
The RMS voltage V in volts is equal to the power P in watts, divided by the PF times the phase current I in amps:
V(V) = 1000 × P(kW) / (PF × I(A) )
So volts are equal to watts divided by power factor times amps.
volts = 1000 × kilowatts / (PF × amps)
or
V = 1000 × W / (PF × A)
Example
What is the RMS voltage in volts when the power consumption is 4 kilowatts, the power factor is 0.8 and the phase current is 3.75 amps?
V = 1000 × 4kW / (0.8 × 3.75A) = 1333.333V
AC three phase watts to volts calculation formula
The line to line RMS voltage VL-L in volts is equal to the power P in kilowatts, divided by square root of 3 times the PF times the phase current I in amps:
VL-L(V) = 1000 × P(kW) / (√3 × PF × I(A) )
So volts are equal to kilowatts divided by square root of 3 times power factor times amps.
volts = 1000 × kilowatts / (√3 × PF × amps)
or
V = 1000 × kW / (√3 × PF × A)
Example
What is the RMS voltage in volts when the power consumption is 4 kilowatts, the power factor is 0.8 and the phase current flow is 2.165 amps?
V = 1000 × 4kW / (√3 × 0.8 × 2.165A) = 1333V